These tools will no longer be maintained as of December 31, 2024. Archived website can be found here. PubMed4Hh GitHub repository can be found here. Contact NLM Customer Service if you have questions.
Pubmed for Handhelds
PUBMED FOR HANDHELDS
Search MEDLINE/PubMed
Title: Neonatal intensive care unit sound levels before and after structural reconstruction. Author: Krueger C, Schue S, Parker L. Journal: MCN Am J Matern Child Nurs; 2007; 32(6):358-62. PubMed ID: 17968218. Abstract: PURPOSE: This study compared sound levels before and after structural reconstruction within an NICU. STUDY DESIGN AND METHODS: Using a descriptive design, sound level recordings (in decibels, A-weighted scale) of the Leq, L10, and Lmax were measured continuously for 8 hours (0600-1400) before and after reconstruction in an NICU located in north central Florida. RESULTS: Levels before reconstruction were Leq M = 60.44 dB, L10 M = 59.26 dB, and Lmax M = 78.39 dB. The average overall sound levels after reconstruction were Leq M = 56.4 dB, L10 M = 60.6 dB, and LmaxM = 90.6 dB. Although an approximate 4-decibel decrease in the Leq sound level after reconstruction was noted, a similar decrease in the L10 and Lmax did not occur. Furthermore, sound levels after reconstruction in the NICU still exceeded recommended levels (Leq < 50 dB, L10 < 55 dB, and Lmax < 70 dB). CLINICAL IMPLICATIONS: Findings from this study demonstrated the positive impact that reconstruction can have on sound levels (4 dB Leq decrease); however, additional interventions may be needed to meet the current standards for noise reduction in an NICU.[Abstract] [Full Text] [Related] [New Search]