These tools will no longer be maintained as of December 31, 2024. Archived website can be found here. PubMed4Hh GitHub repository can be found here. Contact NLM Customer Service if you have questions.
Pubmed for Handhelds
PUBMED FOR HANDHELDS
Search MEDLINE/PubMed
Title: Legionella pneumophila serogroup 1 in a birthing pool. Author: Teare L, Millership S. Journal: J Hosp Infect; 2012 Sep; 82(1):58-60. PubMed ID: 22854354. Abstract: This report describes a risk assessment and subsequent actions following isolation of Legionella pneumophila serogroup 1 in the water supply to a birthing pool during a planned maintenance programme. A literature search for cases of neonatal legionellosis identified 24 reports of cases among babies aged <2 months, two of which were associated with water births. On this basis, the pool was closed until Legionella spp. were undetectable. Control proved difficult as hyperchlorination failed, and a filter fitted to the thermostatic mixer tap supplying the pool slowed filling so much that additional taps were required to achieve a satisfactory flow rate.[Abstract] [Full Text] [Related] [New Search]