These tools will no longer be maintained as of December 31, 2024. Archived website can be found here. PubMed4Hh GitHub repository can be found here. Contact NLM Customer Service if you have questions.


PUBMED FOR HANDHELDS

Search MEDLINE/PubMed


  • Title: Maintenance of cooling towers following two outbreaks of Legionnaires' disease in a city.
    Author: Bhopal RS, Barr G.
    Journal: Epidemiol Infect; 1990 Feb; 104(1):29-38. PubMed ID: 2307183.
    Abstract:
    This survey assessed the maintenance of evaporative cooling towers in Glasgow, following two Legionnaires' disease outbreaks. Information was obtained from 76 of 81 premises and a maintenance score was calculated for each of 174 towers. The quality of maintenance was extremely varied (range of maintenance scores, 8-30; mean, 22 (S.D., 5.0); median, 23; maximum possible, 33) and some towers were neglected. Breaches of maintenance principles were mainly structural and organizational, e.g. inadequate drift control, rather than failure to use chemicals. Low maintenance scores were associated with no log book, no guidelines, no change in procedures in last 5 years, solitary cooling towers, and towers on industrial premises. Despite intense publicity the standard of cooling tower maintenance in Glasgow remained a concern. Information campaigns directed at those responsible for cooling-tower maintenance are necessary.
    [Abstract] [Full Text] [Related] [New Search]