These tools will no longer be maintained as of December 31, 2024. Archived website can be found here. PubMed4Hh GitHub repository can be found here. Contact NLM Customer Service if you have questions.
Pubmed for Handhelds
PUBMED FOR HANDHELDS
Search MEDLINE/PubMed
Title: Removal of higher molecular weight organic compounds by the granular activated carbon adsorption unit process. Author: Stevens AA, Seeger DR, DeMarco J, Moore L. Journal: J Environ Pathol Toxicol Oncol; 1987; 7(7-8):363-72. PubMed ID: 3694484. Abstract: The granular activated carbon adsorption unit process in drinking water treatment typically removes purgeable organic compounds for time periods on the order of a few weeks. Experimental evidence indicates that less volatile compounds of generally higher molecular weight than the purgeable fraction, but still detectable by gas chromatography, are efficiently removed for longer periods. Field data substantiate this. Explanatory mechanisms may include stronger adsorption affinities or biodegradation. Non-gas chromatographable, higher molecular weight materials such as humic acids, as measured by Total Organic Carbon (TOC) or trihalomethane formation potential, revert to lower removal efficiencies. Biodegradation may be responsible for a continued long term removal of a fraction of these materials.[Abstract] [Full Text] [Related] [New Search]