These tools will no longer be maintained as of December 31, 2024. Archived website can be found here. PubMed4Hh GitHub repository can be found here. Contact NLM Customer Service if you have questions.


PUBMED FOR HANDHELDS

Search MEDLINE/PubMed


  • Title: Improved local exhaust control by directed push-pull ventilation system.
    Author: Hampl V, Hughes RT.
    Journal: Am Ind Hyg Assoc J; 1986 Jan; 47(1):59-65. PubMed ID: 3946201.
    Abstract:
    Experiments using the directed push-pull ventilation technique were conducted on a general type of local exhaust ventilation installation. The exhaust (pull) system consisted of a square hood, while the push system consisted of one or two slot jets or two round jets. The two slot or round jets were located behind and beside a mannequin (the mannequin simulated the worker's position). The one slot jet was located between the smoke source and the mannequin. Under experimental conditions, the push-pull system reduced the amount of smoke in the mannequin's breathing zone even when the exhaust system volume flow rate necessary for capture of the smoke decreased approximately 50%. Generally, no difference between the slot and round jet control performance was found. The experiments showed that the directed push-pull ventilation system can be used effectively to reduce the contaminant emission into a workroom, if the jets are located so that the eddy currents induced by the worker or other obstructions are minimized or eliminated.
    [Abstract] [Full Text] [Related] [New Search]