These tools will no longer be maintained as of December 31, 2024. Archived website can be found here. PubMed4Hh GitHub repository can be found here. Contact NLM Customer Service if you have questions.
Pubmed for Handhelds
PUBMED FOR HANDHELDS
Search MEDLINE/PubMed
Title: Evaluation of industrial local exhaust hood efficiency by a tracer gas technique. Author: Hampl V. Journal: Am Ind Hyg Assoc J; 1984 Jul; 45(7):485-90. PubMed ID: 6464994. Abstract: Efficiency of industrial local exhaust ventilation is defined as the ratio of air contaminant quantity captured by the system per unit time to the total contaminant quantity produced by the process per unit time. To date, no direct method exists for this evaluation. This paper describes a tracer gas technique, using sulfur hexafluoride (SF6), which has been developed for the evaluation of local exhaust system efficiency. SF6 was discharged at a known rate into the industrial process generation area. Then, by comparing this quantity to that captured by the exhaust system, as measured in the exhaust duct, hood efficiency is determined. Major advantages of this technique are: The tracer gas technique is able to evaluate directly the hood efficiency. The tracer gas technique is not affected by cross-contamination from nearby industrial processes. The tracer gas technique can be conducted "on site" with minimal interruption of industrial process or interference with workers' duties. The tracer gas, using SF6 is non-toxic. Since SF6 is a gas, this technique may be limited to efficiency evaluation of hoods associated with gases, fumes, vapors, or fine particles.[Abstract] [Full Text] [Related] [New Search]