Title: [The effect of the ventilation rate on air particle and air microbe concentration in operating rooms with conventional ventilation. 1. Measurement without surgical activity]. Author: Kruppa B, Rüden H. Journal: Zentralbl Hyg Umweltmed; 1993 May; 194(3):236-46. PubMed ID: 8338613. Abstract: The question was if a reduction of airborne particles and bacteria in conventionally (turbulently), ventilated operating theatres in comparison to Laminar-Airflow (LAF) operating theatres does occur at high air-exchange-rates. Within the framework of energy consumption measures the influence of air-exchange-rates on airborne particle and bacteria concentrations was determined in two identical operating theatres with conventional ventilation (wall diffusor panel) at the air-exchange-rates 7.5, 10, 15 and 20/h without surgical activity. This was established by means of the statistical procedure of analysis of variance. Especially for the comparison of the air-exchange-rates 7.5 and 15/h statistical differences were found for airborne particle concentrations in supply and ambient air. Concerning airborne bacteria concentrations no differences were found among the various air-exchange-rates. Explanation of variance is quite high for non-viable particles (supply air: 37%, ambient air: 81%) but negligible for viable particles (bacteria) with values below 15%.[Abstract] [Full Text] [Related] [New Search]